Cold Room & Refrigeration Sizing Calculator

Engineering tool for cold storage heat load, evaporator, and compressor specification

Based on ASHRAE Fundamentals & Industrial Refrigeration Standards

Cold Room Heat Load Calculator

Calculate the total refrigeration load for your cold storage facility. Select a preset or configure all parameters manually.

A. Room Dimensions & Insulation

B. Product Load

C. Infiltration Load

D. Miscellaneous Loads

E. Safety Factor

Calculation Results

Load Breakdown

Wall / Ceiling / Floor Heat Gain:
Q_walls = Σ(U × A × ΔT) / 1000   [kW]
Where: U = thermal transmittance (W/m²·K), A = surface area (m²), ΔT = T_ambient – T_storage (°C)
Product Heat Load (cooling above freezing):
Q_product = m × Cp_above × (T_inlet – T_storage) / (t_op × 3600)   [kW]
Product Heat Load (freezing below freezing point):
Q_product = m × [Cp_above × (T_inlet – T_freeze) + L_f + Cp_below × (T_freeze – T_storage)] / (t_op × 3600)   [kW]
Infiltration Load (simplified ASHRAE):
Q_inf = 0.221 × A_door × √H_door × (T_amb – T_storage)^1.5 × D_factor × n_openings × t_open / 86400   [kW]
Miscellaneous Loads:
Q_misc = (Lighting × A_floor + Personnel × W_person × hrs/24 + Equipment + Fans) / 1000   [kW]
Total with Safety Factor:
Q_total = (Q_walls + Q_product + Q_inf + Q_misc) × (1 + SF/100)   [kW]
Recommended Compressor = Q_total × 1.15   [kW]

Evaporator (Unit Cooler) Sizing

Size evaporators based on the total cooling load. Capacity is automatically carried over from the Heat Load tab, or enter manually.

Evaporator Results

⚠️
Correction Note: Manufacturer evaporator ratings are typically given at a standard TD of 8K or 10K. When operating at a different TD, apply the manufacturer’s correction factor. Capacity is approximately proportional to TD ratio.
Required Capacity Per Evaporator:
Q_evap = Q_total / n_evaporators   [kW]
Evaporating Temperature:
T_evap = T_storage – TD   [°C]
Rated Capacity at Standard TD (correction):
Q_rated = Q_evap × (TD_standard / TD_actual)   [kW]
Where TD_standard is typically 8K or 10K per manufacturer datasheet
Defrost Derating:
Electric defrost: ~5% capacity loss
Hot gas defrost: ~3% capacity loss
Air defrost: ~8% capacity loss
Off-cycle: ~10% capacity loss

Common Cold Room Parameters

Standard design parameters for typical cold storage applications.

Application Temp (°C) RH (%) Insulation Typical Size Notes
Meat Freezer-18 to -2290PU 150–200mm50–500 m²Must maintain -18°C core temp
Dairy0 to 485–90PU 100mm20–200 m²Separate from strong odors
Fruit & Veg0 to 885–95PU 100mm30–300 m²Ethylene control needed
Blast Freezer-35 to -4090PU 200mm10–100 m²High refrigeration rate
Pharmaceutical2 to 845–65PU 100mm10–50 m²GDP compliance required
Beer / Beverage0 to 465–75PU 100mm20–200 m²CO&sub2; ventilation needed
Ice Cream-25 to -30—PU 200mm20–150 m²Consistent temp critical
Industrial5 to 10—PU 100mm50–1000 m²Varies by process

Insulation U-Values

Thermal transmittance for common cold room insulation materials.

Material Thickness (mm) U-value (W/m²·K)
PU Panel750.29
PU Panel1000.22
PU Panel1250.18
PU Panel1500.16
PU Panel1750.13
PU Panel2000.12
EPS1000.35
EPS1500.24
XPS1000.30

Product Thermal Properties

Specific heat and latent heat values for common cold-stored products (ASHRAE data).

Product Cp Above Freezing (kJ/kg·K) Cp Below Freezing (kJ/kg·K) Latent Heat Lf (kJ/kg) Freezing Point (°C)
Beef3.081.67249-1.7
Pork2.851.55241-2.2
Chicken3.311.76247-2.8
Fish3.601.86276-2.0
Milk3.931.95281-0.5
Cheese2.101.35167-6.0
Apple3.731.88279-1.5
Lettuce4.061.94290-0.2
Beer3.852.00264-2.0

Watch: Cold Room: Why Pull-Down Time Changes Capacity

This example covers warm-product pull-down load only. Its numerical examples are not equipment ratings or a complete cold-room load calculation.

Illustrative procurement and selection guide; not product footage or performance test evidence. Confirm the final specification for your application.

Send product type and daily intake, entry and target temperatures, cooling time, room construction and door usage. Request a quotation: sales@hiqool.com

Need a Refrigeration System Quotation?

From cold room design to compressor packages — our engineers deliver complete solutions.

Request a Quote →
Hicool supplies industrial & marine refrigeration equipment worldwide
sales@hiqool.com  |  +86 523 87625500  |  www.hiqool.com

Disclaimer: Calculations are based on ASHRAE Handbook of Fundamentals and industry best practices. Results are preliminary engineering estimates for reference only. Final system design must be verified by a qualified refrigeration engineer. Operating conditions, product specifics, and local regulations may require adjustments to these calculations.

© 2026 Hicool Machinery Co., Ltd. — Industrial & Marine Equipment Solutions